RTS Switch KGATX0101400 User Guide

RTS Automatic Transfer Switch  
400A, 120/240V, Single-phase  
Model No.: KGATX0101400  
TECHNICAL  
MANUAL  
A new standard of reliability  
This manual should remain with the unit.  
 
Table of Contents  
• Because jewelry conducts electricity, wearing it  
may cause dangerous electrical shock. Remove  
all jewelry (such as rings, watches, bracelets, etc.)  
before working on this equipment.  
• If work must be done on this equipment while  
standing on metal or concrete, place insulative  
mats over a dry wood platform. Work on this  
equipment only while standing on such insulative  
mats.  
Safety Rules .........................................Inside Front Cover  
Section 1 — General Information ...................................2  
1.1 Introduction............................................................. 2  
1.2 Equipment Description ........................................... 2  
1.3 Transfer Switch Data Label..................................... 2  
1.4 Transfer Switch Enclosure ...................................... 2  
1.5 Safe Use of Transfer Switch .................................... 2  
Section 2 — Installation....................................................3  
2.1 Introduction to Installation...................................... 3  
2.2 Unpacking ............................................................... 3  
2.3 Mounting ................................................................. 3  
2.4 Connecting Power Source and Load Lines............... 3  
2.4.1 2-Pole Mechanism ......................................... 3  
2.5 Connecting Start Circuit Wires ................................ 4  
2.6 Auxiliary Contacts.................................................... 4  
Section 3 — Operation.......................................................4  
3.1 Functional Tests & Adjustments.............................. 4  
3.2 Manual Operation.................................................... 5  
3.2.1 Close to Normal Source Side ........................ 5  
3.2.2 Close to Emergency Source Side................... 6  
3.2.3 Return to Normal Source Side ...................... 6  
3.3 Voltage Checks......................................................... 6  
3.3.1 Utility Voltage Checks.................................... 6  
3.3.2 Generator Voltage Checks.............................. 6  
3.4 Generator Tests Under Load ................................... 7  
Section 4 – Installation Diagram....................................8  
Section 5 – Electrical Data...............................................9  
Section 6 – Exploded Views & Parts Lists..................12  
Section 7 – Warranty ......................................Back Cover  
• Never work on this equipment while physically or  
mentally fatigued.  
• Keep the transfer switch enclosure door closed  
and bolted at all times. Only qualified personnel  
should be permitted access to the switch interior.  
• In case of an accident caused by electric shock,  
immediately shut down the source of electrical  
power. If this is not possible, attempt to free the  
victim from the live conductor but AVOID DIRECT  
CONTACT WITH THE VICTIM. Use a nonconduct-  
ing implement, such as a rope or board, to free  
the victim from the live conductor. If the victim  
is unconscious, apply first aid and get immediate  
medical help.  
• When an automatic transfer switch is installed for  
a standby generator set, the generator engine may  
crank and start at any time without warning. To  
avoid possible injury that might be caused by such  
sudden start-ups, the system’s automatic start cir-  
cuit must be disabled before working on or around  
the generator or transfer switch. Turn the genera-  
tor’s AUTO/OFF/MANUAL switch to OFF. Turn the  
generator’s main circuit breaker OFF. Then place  
a “DO NOT OPERATE” tag on the transfer switch  
and on the generator. Remove the Negative (Neg) or  
(–) battery cable.  
1
 
Section 1 — General Information  
RTS “W” Type Transfer Switch  
1.1 INTRODUCTION  
1.3 TRANSFER SWITCH DATA LABEL  
A DATA LABEL is permanently affixed to the transfer  
switch enclosure. Use this transfer switch only with  
the specific limits shown on the DATA LABEL and  
on other decals and labels that may be affixed to the  
switch. This will prevent damage to equipment and  
property.  
This manual has been prepared especially for the  
purpose of familiarizing personnel with the design,  
application, installation, operation and servicing of  
the applicable equipment. Read the manual carefully  
and comply with all instructions. This will help to  
prevent accidents or damage to equipment that might  
otherwise be caused by carelessness, incorrect appli-  
cation, or improper procedures.  
When requesting information or ordering parts for this  
equipment, make sure to include all information from  
the DATA LABEL.  
Every effort has been expended to make sure that the  
contents of this manual are both accurate and cur-  
rent. The manufacturer reserves the right to change,  
alter or otherwise improve the product at any time  
without prior notice.  
Record the Model and Serial numbers in the space  
provided below for future reference.  
MODEL #  
SERIAL #  
1.2 EQUIPMENT DESCRIPTION  
The automatic transfer switch is used for transferring  
critical electrical loads from a UTILITY (NORMAL)  
power source to an EMERGENCY (GNERATOR)  
power source.  
The transfer switch prevents electrical feedback  
between the UTILITY and EMERGENCY sources. For  
that reason, electrical codes require a transfer switch  
in all standby electric system installations.  
1.4 TRANSFER SWITCH ENCLOSURE  
The standard switch enclosure is a National Electrical  
Manufacturer’s Association (NEMA) and UL 3R type.  
UL and NEMA 3R type enclosures primarily provide  
a degree of protection against falling rain and sleet;  
undamaged by the formation of ice on the enclosure.  
When the transfer switch is connected to the engine  
generator control panel, the control panel constantly  
monitors the UTILITY voltage and controls the opera-  
tion of the transfer switch.  
Should the UTILITY voltage drop below a preset value,  
and remain at this low voltage for a preset amount of  
time, the generator cranks and starts. After the gen-  
erator starts, the transfer switch transfers the load  
circuits to the generator, the generator then supplies  
the loads. When UTILITY returns above a preset level  
the load is transferred back to the UTILITY and the  
generator shuts down.  
1.5 SAFE USE OF TRANSFER SWITCH  
Before installing, operating or servicing this equip-  
ment, read the SAFETY RULES (inside front cover)  
carefully. Comply strictly with all SAFETY RULES  
to prevent accidents and/or damage to the equip-  
ment. The manufacturer recommends a copy of the  
SAFETY RULES are made and posted near the trans-  
fer switch. Also, be sure to read all instructions and  
information found on tags, labels and decals affixed  
to the equipment.  
Two publications that outline the safe use of transfer  
switches are the following:  
• NFPA 70; National Electrical Code  
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC  
TRANSFER SWITCHES  
NOTE:  
It is essential to use the latest version of any stan-  
dard to ensure correct and current information.  
2
 
Section 2 — Installation  
RTS “W” Type Transfer Switch  
2.4.1 2-POLE MECHANISM  
2.1 INTRODUCTION TO INSTALLATION  
This equipment has been wired and tested at the  
factory. Installing the switch includes the following  
procedures:  
These switches (Figure 2.1) are used with a single  
phase system, when the single phase NEUTRAL line  
is to be connected to a Neutral Lug and is not to be  
switched.  
• Mounting the enclosure.  
• Connecting utility and generator power source  
Figure 2.1 — Typical 2-Pole Transfer Mechanism  
(400 Amp Shown)  
leads.  
• Connecting the load leads.  
• Connecting any auxiliary contact (if needed)  
• Installing/connecting any options and accessories.  
Testing functions.  
2.2 UNPACKING  
Carefully unpack the transfer switch. Inspect closely  
for any damage that might have occurred during ship-  
ment. The purchaser must file with the carrier any  
claims for loss or damage incurred while in transit.  
Check that all packing material is completely removed  
from the switch prior to installation.  
2.3 MOUNTING  
Mounting dimensions for the transfer switch enclo-  
sure are in this manual. Enclosures are typically wall-  
mounted. See the “Mounting Dimensions” drawing.  
Handle transfer switches carefully when install-  
ing. Do not drop the switch. Protect the switch  
against impact at all times, and against construc-  
tion grit and metal chips. Never install a transfer  
switch that has been damaged.  
Install the transfer switch as close as possible to the  
electrical loads that are to be connected to it. Mount  
the switch vertically to a rigid supporting structure.  
To prevent switch distortion, level all mounting  
points. If necessary, use washers behind mounting  
holes to level the unit.  
Solderless, screw-type terminal lugs are standard.  
The conductor size range is as follows:  
Switch Rating  
Wire Range  
(1) #4-600 MCM or  
(2) 1/0-250 MCM  
400A  
Conductor sizes must be adequate to handle the max-  
imum current to which they will be subjected; based  
on the 75°C column of tables, charts, etc. used to size  
conductors. The installation must comply fully with  
all applicable codes, standards and regulations.  
2.4 CONNECTING POWER SOURCE  
AND LOAD LINES  
DANGER  
Before connecting wiring cables to terminals, remove  
any surface oxides from the cable ends with a wire  
brush. All power cables should enter the switch next  
to transfer mechanism terminals. If ALUMINUM con-  
ductors are used, apply corrosion inhibitor to con-  
ductors. Tighten terminal lugs to the torque values as  
noted on the decal located on the inside of the door.  
After tightening terminal lugs, carefully wipe away  
any excess corrosion inhibitor.  
Make sure to turn OFF both the UTILITY  
(Normal) and EMERGENCY (Standby generator)  
power supplies before trying to connect power  
source and load lines to the transfer switch.  
Supply voltages are extremely high and danger-  
ous. Contact with such high voltage power sup-  
ply lines causes extremely hazardous, possibly  
lethal, electrical shock.  
Wiring diagrams and electrical schematics are pro-  
vided in this manual. Power source and load connec-  
tions are made at the transfer mechanism, inside the  
switch enclosure.  
All power cables should enter the switch next to the  
transfer mechanism terminals.  
3
 
Section 3 — Operation  
RTS “W” Type Transfer Switch  
NOTE:  
Auxiliary Contacts are rated 10 amps at 125 or  
250 volts AC. DO NOT EXCEED THE RATED  
VOLTAGE AND CURRENT OF THE CONTACTS.  
Use a torque wrench to tighten the conductors,  
being sure not to overtighten, or damage to  
the switch base could occur. If undertightened,  
a loose connection would result, causing excess  
heat which could damage the switch base.  
Figure 2.3 – Auxiliary Contacts  
Connect power source load conductors to clearly  
marked transfer mechanism terminal lugs as fol-  
lows  
1. Connect UTILITY (NORMAL) power source cables  
to switch terminals N1, N2, (N3).  
2. Connect EMERGENCY (STANDBY) source power  
cables to transfer switch terminals E1, E2, (E3).  
3. Connect customer LOAD leads to switch termi-  
nals T1, T2, (T3).  
Side views shown in Utility position  
4. Connect neutral conductors of UTILITY,  
EMERGENCY and customer LOAD to the neutral  
block.  
Conductors must be properly supported, of approved  
insulative qualities, protected by approved conduit,  
and of the correct wire gauge size in accordance with  
applicable codes.  
Be sure to maintain proper electrical clearance  
between live metal parts and grounded metal. Allow  
at least 1/2 inch for 100-400 amp circuits.  
2.5 CONNECTING START CIRCUIT  
3.1 FUNCTIONAL TESTS AND  
WIRES  
ADJUSTMENTS  
Control system interconnections consist of UTILITY  
1 and 2, and leads 23 and 194. Control system  
interconnection leads must be run in a conduit that  
is separate from the AC power lead. Recommended  
wire gauge sizes for this wiring depends on the length  
of the wire, as recommended below:  
Following transfer switch installation and intercon-  
nection, inspect the entire installation carefully. A  
competent, qualified electrician should inspect it.  
The installation should comply strictly with all appli-  
cable codes, standards, and regulations. When abso-  
lutely certain the installation is proper and correct,  
complete a functional test of the system.  
MAXIMUM WIRE LENGTH  
RECOMMENDED WIRE  
SIZE  
460 feet (140m)  
No. 18 AWG.  
No. 16 AWG.  
No. 14 AWG.  
No. 12 AWG.  
461 to 730 feet (223m)  
731 to 1,160 feet (354m)  
1,161 to 1,850 feet (565m)  
Perform functional tests in the exact order pre-  
sented in this manual, or damage to the switch  
could be done.  
IMPORTANT: Before proceeding with functional tests,  
read and make sure you understand all instructions  
and information in this section. Also read the infor-  
mation and instructions of labels and decals affixed  
to the switch. Note any options or accessories that  
might be installed and review their operation.  
2.6 AUXILIARY CONTACTS  
If desired, there are Auxiliary Contacts on the transfer  
switch to operate customer accessories, remote advi-  
sory lights, or remote annunciator devices. A suitable  
power source must be connected to the COMMON (C)  
terminal. See Figure 2.3.  
Contact operation is shown in the following chart:  
Switch Position  
Utility  
Open  
Closed  
Standby  
Closed  
Open  
Common to Normally Open  
Common to Normally Closed  
4
 
Section 3 — Operation  
RTS “W” Type Transfer Switch  
• Window A” OFF, Window “B” ON - LOAD termi-  
nals (T1, T2, T3) are connected to emergency  
terminals (E1, E2, E3).  
3.2 MANUAL OPERATION  
DANGER  
Do NOT manually transfer under load.  
Disconnect transfer switch from all power sourc-  
Do not use excessive force when operating the  
transfer switch manually or the manual handle  
could be damaged.  
es by approved means, such as a main circuit  
breaker(s).  
A manual HANDLE is shipped with the transfer  
switch. Manual operation must be checked BEFORE  
the transfer switch is operated electrically. To check  
manual operation, proceed as follows:  
3.2.1 CLOSE TO NORMAL SOURCE SIDE  
Before proceeding, verify the position of the switch  
by observing window A” in Figure 3.1. If window A”  
reads “ON”, the contacts are closed in the normal  
position, no further action is required. If it reads  
“OFF”, proceed with Step 1.  
1. Turn the generator’s AUTO/OFF/MANUAL switch  
to OFF.  
2. Turn OFF both UTILITY and EMERGENCY power  
supplies to the transfer switch, with whatever  
means provided (such as the main line circuit  
breakers).  
3. Note position of transfer mechanism main con-  
tacts by observing display windows in A” and “B”  
in Figure 3.1 on page 6 as follows:  
• Window A” ON, Window “B” OFF - LOAD termi-  
nals (T1, T2, T3) are connected to utility termi-  
nals (N1, N2, N3).  
Step 1: With the handle attached to the actuating  
shaft, move handle in the direction of the  
arrow on the switch cover until it stops  
— DO NOT FORCE. Release handle slowly  
to allow the spring in the switch box to relax.  
“ON” now appears in Window A” and “OFF”  
appears in Window “B”.  
Figure 3.1 — Actuating Transfer Switch  
5
 
Section 3 — Operation  
RTS “W” Type Transfer Switch  
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE  
3.3.2 GENERATOR VOLTAGE CHECKS  
Before proceeding, verify the position of the switch  
by observing window “B” in Figure 3.1. If window  
“B” reads “ON”, the contacts are closed in the  
EMERGENCY (STANDBY) position. No further action  
is required. If it reads “OFF”, proceed with Step 1.  
1. On the generator panel, set the AUTO/OFF/  
MANUAL switch to MANUAL position. The gen-  
erator should crank and start.  
2. Let the generator stabilize and warm up at no-  
load for at least five minutes.  
3. Set the generator's main circuit breaker (CB1) to  
its ON or CLOSED position.  
Step 1: With the handle attached to the actuating  
shaft, move the handle in the direction of the  
arrow on the switch cover until it stops - DO  
NOT FORCE. Release handle slowly to allow  
the spring in the switch box to relax. “OFF”  
now appears in Window A” and “ON” appears  
in Window “B”.  
DANGER  
PROCEED WITH CAUTION. GENERATOR  
OUTPUT VOLTAGE IS NOW BEING DELIVERED  
TO TRANSFER SWITCH TERMINALS. CONTACT  
WITH LIVE TERMINALS RESULTS IN EXTREMELY  
DANGEROUS AND POSSIBLY FATAL ELECTRICAL  
SHOCK.  
3.2.3 RETURN TO NORMAL SOURCE SIDE  
Manually actuate switch to return Window A” to the  
“ON” position.  
4. With an accurate AC voltmeter and frequency  
meter, check the no-load, voltage and frequency.  
Single-phase generator supply:  
3.3 VOLTAGE CHECKS  
Measure across ATS terminal lugs E1 to E2; E1  
to NEUTRAL and E2 to NEUTRAL.  
3.3.1 UTILITY VOLTAGE CHECKS  
a. Frequency.......................................60-62 Hz  
b. Terminals E1 to E2 ........................240-246 VAC  
c. Terminals E1 to NEUTRAL.............120-123 VAC  
d. Terminals E2 to NEUTRAL.............120-123 VAC  
5. When certain that UTILITY supply voltage is cor-  
rect and compatible with transfer switch ratings,  
turn OFF the UTILITY supply to the transfer  
switch.  
1. Turn ON the UTILITY power supply to the trans-  
fer switch with whatever means provided (such as  
the UTILITY maim line circuit breaker).  
DANGER  
PROCEED WITH CAUTION. THE TRANSFER  
SWITCH IS NOW ELECTRICALLY HOT. CONTACT  
6. Set the generator’s main circuit breaker (CB1) to  
WITH LIVE TERMINALS RESULTS IN EXTREMELY  
HAZARDOUS AND POSSIBLY FATAL ELECTRICAL  
SHOCK.  
its OFF or OPEN position.  
7. Set the AUTO/OFF/MANUAL switch to the OFF  
position to shut down the generator.  
2. With an accurate AC voltmeter, check for correct  
voltage.  
NOTE:  
Single-phase utility supply:  
Measure across ATS terminal lugs N1 and N2; N1  
to NEUTRAL and N2 to NEUTRAL.  
Do NOT proceed until generator AC output volt-  
age and frequency are correct and within stated  
limits. If the no-load voltage is correct but no-  
load frequency is incorrect, the engine governed  
speed probably requires adjustment. If no-load  
frequency is correct but voltage is not, the voltage  
regulator may require adjustment.  
DANGER  
FAILURE TO TURN OFF THE UTILITY SUPPLY  
BEFORE WORKING ON THE UTILITY CONNEC-  
TIONS OF THE ATS WILL RESULT IN EXTREMELY  
DANGEROUS AND POSSIBLY FATAL ELECTRICAL  
SHOCK.  
5. When certain that UTILITY supply voltage is cor-  
rect and compatible with transfer switch ratings,  
turn OFF the UTILITY supply to the transfer  
switch.  
6
 
Section 3 — Operation  
RTS “W” Type Transfer Switch  
5. When checkout under load is complete, set main  
circuit breaker of the generator to the OFF or  
OPEN position.  
6. Let the generator run at no-load for several min-  
utes. Then, shut down by setting the AUTO/OFF/  
MANUAL switch to its OFF position.  
7. Move the switch's main contacts back to the  
UTILITY position. For example, load connected to  
utility power supply. Refer to “Manual Operation”.  
Handle and operating lever of transfer switch  
should be in down position.  
8. Turn on the utility power supply to transfer  
switch, using whatever means provided (such  
as a utility main line circuit breaker). The utility  
power source now powers the loads.  
3.4 GENERATOR TESTS UNDER LOAD  
1. Set the generator's main circuit breaker to its  
OFF or OPEN position.  
2. Manually actuate the transfer switch main con-  
tacts to their EMERGENCY (STANDBY) position.  
Refer to “Manual Operation” section.  
3. To start the generator, set the AUTO/OFF/MANUAL  
switch to MANUAL. When engine starts, let it sta-  
bilize for a few minutes.  
4. Turn the generator's main circuit breaker to the  
ON or CLOSED position. The generator now pow-  
ers all LOAD circuits. Check generator operation  
under load as follows:  
Turn ON electrical loads to the full rated watt-  
age/amperage capacity of the generator. DO  
NOT OVERLOAD.  
9. Set the generator's AUTO/OFF/MANUAL switch to  
its AUTO position. The system is now set for fully  
automatic operation.  
With maximum rated load applied, check  
voltage and frequency across transfer switch  
terminals E1 and E2. Voltage should be  
greater than 200 volts (208VAC system) or  
230 volts (240VAC system); frequency should  
be greater than 59 Hz.  
Let the generator run under rated load for at  
least 30 minutes. With unit running, listen for  
unusual noises, vibration, overheating, etc.,  
that might indicate a problem.  
7
 
Section 4 — Installation Diagram  
RTS “W” Type Transfer Switch  
Installation Diagram – Drawing No. 0F6401  
8
 
Section 5 — Electrical Data  
RTS “W” Type Transfer Switch  
Interconnection Diagram - Drawing No. 0G1944  
9
 
Section 5 — Electrical Data  
RTS “W” Type Transfer Switch  
Wiring Diagram/Schematic – Drawing No. 0D3819-A  
TR  
1
F1  
F2  
N1  
N2  
126  
N1A  
N1A  
7
N2A  
N2A  
126  
N1A  
A1  
B1  
T1 T2  
205  
LS1  
2
3
5
6
LS3  
6
RED  
TR  
9
N2A  
WHITE  
1
4
E1  
LS2  
GT
S
 
A2  
B2  
E1  
E2  
N2A  
23  
23  
B
LEGEND  
TR  
A
C - CONTACTOR ACTUATING COIL  
GTS - TRANSFER SWITCH CONTACTOR  
194  
194  
TR - RELAY, TRANSFER  
TS - TERMINAL STRIP (CUSTOMER CONNECTION)  
LS1,LS2,LS3 - LIMIT SWITCHES, ACTUATOR  
F1,F2 - FUSE 5A SENSING  
NOTES:  
ALL CONTACTS SHOWN WITH  
TRANSFER SWITCH IN UTILITY  
POSITION.  
10  
 
Section 5 — Electrical Data  
RTS “W” Type Transfer Switch  
Wiring Diagram/Schematic – Drawing No. 0D3819-A  
N2A  
N2A  
N1A  
N1A  
N1  
N2  
GT
S
 
N1A  
E1  
T1  
E2  
T2  
N2A  
E2  
N2A  
205  
N2A  
E1  
126  
N1A  
N1A  
126  
TR  
205  
A
B
7
9
1
3
N2A  
194  
N1A  
23  
205  
E1  
23  
194  
N1A  
N2A  
N1A  
N1A  
N2A  
F2  
23  
194  
N1  
23  
N2  
194  
T
S  
11  
 
Section 6 — Exploded Views and Parts List  
RTS “W” Type Transfer Switch  
400 A Switch Assembly – Drawing No. 0G1510$  
12  
 
Section 6 — Exploded Views and Parts List  
RTS “W” Type Transfer Switch  
400 A Switch Assembly – Drawing No. 0G1510$  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
0D7294  
0A7822  
026902  
0C7907J  
024526  
057329  
027482  
022097  
0C8275  
0D2806  
090388  
0A1495  
063617  
047411  
0A1661  
0F4034  
0F5935  
0F5939  
0C8308  
0C2262  
0F6165  
0G1520  
064101  
0F5940  
087680  
063378  
064761  
063321  
073590A  
0D3587  
067210A  
0A9457  
0D4545  
0F6129  
081221  
0A8261  
022473  
048850  
0F6273A  
022129  
091472  
091472A  
067989  
1
6
5
2
1
1
1
9
4
1
3
6
1
2
2
1
1
1
2
1
2
1
6
1
1
4
4
1
2
1
1
1
1
1
1
6
6
1
1
1
2'  
2'  
2
XFER SW-W 400A600V2P  
LUG, SLDLSS 600/250-1/0X1/4-28  
SCREW TAPTITE #8-32X1/4 BP  
COVER LUG 2P 400AMP  
3
4
5
SCREW HHTT 5/16-18 X 3/4 CZ  
LUG, SOLDERLESS 350-#6X13/32 AL/CU  
WASHER SHAKEPROOF EXT 5/16 STEEL  
WASHER LOCK M6-1/4  
6
7
8
9
SCREW PPHM DSEMS M4-.7 X 10 ZNC  
FUSEBLOCK 30A 600V 2POS W/SQ  
SCREW TAPTITE M6-1.0 X 12 MM  
SCREW TAPTITE M4-.7 X 10 MM  
RELAY PNL 12VDC DPDT 10A@240VA  
SCREW HHC M6-1.0 X 16 G8.8  
RIVET, POP  
(2) 10  
11  
12  
(2) 13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
(1) 34  
35  
36  
37  
(2) 38  
39  
40  
41  
42  
43  
ASSY. NEUTRAL BLOCK 300/400A  
RTS 3R ENCLOSURE 24X36X10  
COVER TRANSFER SWITCH  
DECAL TERMINAL SHOCK HAZARD  
DECAL TERMINAL STRIP  
WASHER, NYLON  
DECAL,DATA XFER SW 400A,240V  
NUT HEX FL WHIZ 3/8-16  
SUBPLATE,100A TS 3R 480V  
NUT WING M6-1.0  
HOLDER CABLE TIE  
TIE WRAP UL 5.6" X .10" NATL  
HANDLE TRANSFER SWITCH 1-400A  
FUSE 5A X BSS HLDR73591  
DECAL,FUSE REPLACEMENT  
DECAL GROUND LUG  
DECAL NEUTRAL  
DECAL MANUAL OPERATION  
DECAL, TEST SEQUENCE  
DECAL, UL NAMEPLATE  
SCREW, HHCS 1/4-28 X 5/8"  
WASHER, FLAT 1/4-6M ZINC  
BLOCK TERM 20A 5 X 6 X 1100V  
HARNESS 400A 2 POLE RTS (NOT SHOWN)  
WASHER LOCK M8-5/16  
DUCT WIRING 1X1.5  
COVER WIRE DUCT 1 IN  
NUT HEX FL WHIZ M8-1.25  
(1) CENTER DECAL ON INSIDE OF THE COVER (ITEM #18)  
(2) ITEMS INCLUDED WITH HARNESS  
13  
 
Section 8 — Warranty  
RTS “W” Type Transfer Switch  
CARRIER WARRANTY/SERVICE  
Carrier will warrant that from the date of purchase, our transfer switch will be free from  
defects in material and workmanship for the items and periods set forth in the warranty  
statement found in the owners manual of the Carrier generator that this transfer switch  
will be utilized with.  
Any equipment that the purchaser/owner claims to be defective must be examined by the  
nearest Carrier Dealer.  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR  
IMPLIED, SPECIFICALLY, CARRIER MAKES NO OTHER WARRANTIES AS TO THE  
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  
Some states do not allow limitations on how long an implied warranty lasts, so the above  
limitation may not apply to you.  
CARRIER’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS  
STATED ABOVE. IN NO EVENT SHALL CARRIER BE LIABLE FOR ANY INCIDENTAL, OR  
CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF  
CARRIER’S NEGLIGENCE.  
Some states do not allow the exclusion or limitation of incidental or consequential dam-  
ages, so the above limitations may not apply to you.  
This warranty gives you specific legal rights. You also may have other rights that vary from  
state to state.  
Part No. 0G1622  
Rev. A (12/15/06)  
Catalog No. OMKGATD,XNS400-03  
Printed in U.S.A.  
 

Ricoh Printer BY1000 User Guide
Ricoh Printer SP 4110N User Guide
Rikaline GPS Receiver GPS 24 24A User Guide
Rosewill Network Card RC 303 User Guide
Samsung Digital Camera WB800F User Guide
Samsung Printer 835P User Guide
Sangean Electronics Portable Radio ATS 404 User Guide
Sanyo Battery Charger KR 1100AAU User Guide
Schumacher Power Supply IP 1825FL User Guide
Scientific Atlanta Network Router Rosa User Guide